Skip to main content

Science – Society – Technology

Table 3 Detailed parameters measured from the TRTs

From: Operational strategies to alleviate thermal impacts of the large-scale borehole heat exchanger array in Beijing Daxing Airport

Well

Mean temperature difference (K)

Flow flux (m3/h)

Heating power (W)

Heating power/BHE length (W/m)

Regression curve

Thermal conductivity coefficient [W/(m·K)]

#3

4.19

1.52

7430.3

53.1

y = 2.45x + 2.10

1.72

#4

4.36

1.55

7884.3

56.3

y = 2.97x − 4.70

1.51

#5

4.50

1.55

8137.5

58.1

y = 2.36x + 3.43

1.96

#6

4.28

1.50

7490.0

53.5

y = 3.27x − 8.56

1.30